  • "Battery replaced" date in device properties of PowerChute Business Edition shows incorrect date such as 01.01.1980
    After replacing the battery pack:<br />
    <br />
    shutdown UPS monitoring tool.<br />
    <br />
    connect with a terminal program (hyperterminal or gtkterm).<br />
    <br />
    2400 baud, 8N1, flow Xon/Xoff<br />
    <br />
    Type &quot;Y&quot;<br />
    UPS should return &quot;SM&quot;<br />
    Type &quot;x&quot;<br />
    UPS should return battery date.<br />
    Type &quot;-MM/DD/YY&quot; (e.g. &quot;-02/24/11&quot;) to set the new battery date<br />
    Type &quot;x&quot;<br />
    UPS should return new battery date<br />
    <br />
    close terminal program and restart UPS monitoring tool.
    (tags: apc usv ups battery)